Malingssystemer og godkjenninger for brannbeskyttelse av stål
Her finner du brannhemmende malingssystemer for brannbeskyttelse av stålstrukturer og Hensotherm® godkjenninger for hvert land.
Malingssystemer
Indoor - Water-based |
Fire class | VOC g/l | Vol. solids % | |
Primer | Water-based acrylic primers, Alkyd primers & Epoxy primers | |||
Intumescent paint |
HENSOTHERM® 410/421 KS
|
R30-R120 | about 0 | 70 |
Top coat | TEKNOCRYL 100, TEKNOCRYL AQUA COMBI 2780, BIORA series, TEKNOLAC COMBI 151 |
Outdoor - Solvent-based | Fire class | VOC g/l | Vol. solids % | |
Primer | Alkyd primers & Epoxy primers | |||
Intumescent paint |
HENSOTHERM® 310/320 KS
|
R30-R120 | 350 | 73 |
Top coat | TEKNOCRYL 100, TEKNODUR 0050, TEKNOLAC COMBI 151, Emapur PS 60 5 |
Outdoor/Indoor - Solvent-free | Fire class | VOC g/l | Vol. solids % | |
Primer | TEKNOPLAST PRIMER 5 (when primer is needed) | |||
Intumescent paint |
HENSOTHERM® 910 KS
|
R30-R60 | 0 | 100 |
Top coat | TEKNOCRYL 100, TEKNODUR 0050, Emapur PS 60 5 & BIORA Series |
Hensotherm® godkjenninger for hvert land
HENSOTHERM® brannbeskyttende/svellende maling for stål er godkjent av byggemyndighetene i samsvar med EN europeisk standard og DIN-standard fra det tyske institutt for standardisering, og har ytterligere internasjonale sertifikater i henhold til Vereinigung Kantonaler Feuerversicherungen VKF for bruk i Sveits, Britisk standard BS 476 for bruk i Europa og Midtøsten, Underwriters Laboratories UL 263 for bruk i USA og Canada, og Gossudarstwenny Standard GOST for bruk i områdene som tilhører den russiske føderasjonen.
Country | Product Names | Fire Resistant Class | |
Austria, Belgium, Croatia, Denmark, Estonia, Finland | Hensotherm® 310 KS and 410 KS | R30 – R60 | acc. to ETA |
Hensotherm® 320 KS and 420 KS | R90 – R120 | acc. to ETA | |
Germany | Hensotherm® 310 KS and 410 KS | R30 – R60 | according to ETA |
Hensotherm® 320 KS and 420 KS | R90 – R120 | according to ETA | |
Hensotherm® 3 KS and 4 KS | F30 – F60 | according to DIN 4102 | |
Hensotherm® 3 KS | F90 | according to DIN 4102 | |
Hungary | Hensotherm® 310 KS and 410 KS | R30 – R60 | ETA with EMI Nostrifizierung |
Hensotherm® 320 KS and 420 KS | R90 – R120 | ETA with EMI Nostrifizierung | |
Ireland | Hensotherm® 370 KS and 460 | F30 – F60 | according to British standard |
Hensotherm® 370 KS and 470 KS | F90 – F120 | according to British standard | |
Latvia, Lithuania Netherlands, Norway, Poland Romania |
Hensotherm® 310 KS and 410 KS | R30 – R60 | according to ETA |
Hensotherm® 320 KS and 420 KS | R90 – R120 | according to ETA | |
Russia | Hensotherm® 30 KS and 40 KS | R45 – R120 | according to GOST |
Slovenia | Hensotherm® 310 KS and 410 KS | R30 – R60 | according to ETA |
Hensotherm® 320 KS and 420 KS | R90 – R120 | according to ETA | |
Sweden | Hensotherm® 310 KS and 410 KS | R30 – R60 | according to ETA |
Hensotherm® 320 KS and 420 KS | R90 – R120 | according to ETA | |
Hensotherm® 3 KS and 4 KS | R30 – R120 | according to Swedcert | |
Switzerland | Hensotherm® 3 KS and 4 KS | F30 – F60 | according to VKF (DIN 4102) |
Hensotherm® 310 KS and 410 KS | R30 – R60 | ETA with VKF Nostrifizierung | |
Hensotherm® 320 KS and 420 KS | R90 – R120 | ETA with VKF Nostrifizierung | |
United Kingdom | Hensotherm® 370 KS and 460 KS | F30 – F60 | according to British standard |
Hensotherm® 370 KS and 470 KS | F90 – F120 | according to British standard |